Fabricated Clevis Hangers are manufactured from glass-reinforced polyester and are available for size 1″ through 24″.
Fabricated Clevis Hanger Spec Chart
Not sure where to start? Let our experts lead the way and help you design an application that fits your needs. From engineering to fabrication, Unistrut Midwest is there to help you get the job done right. Feel free to give us a call or shoot us an email with any questions you might have!
Aickinstrut Fiberglass Framing Catalog
Click Here for Fiberglass Channel
Click Here for Fiberglass Fittings
Material Codes:
- P – Polyester (pultruded)
- V – Vinyl Ester (pultruded)
- E – PVC (extruded)
- PU – Polyurethane (injection molded)
- PP – Polypropylene (injection molded)
- N – Nylon (injection molded)
Polyester and Vinyl ester Materials:
- Polyester and vinyl ester channels are manufactured from the pultrusion process and are color-coded gray and beige respectively. Components are made by reinforcing a polymer resin (polyester or vinyl ester) with multiple strands of glass filament, alternating layers of glass mat, and U.V. resistant surfacing veils. The glass is drawn through the liquid resin, which coats and saturates the fibers. The combination of resin, glass, and veil is then continuously guided and pulled (pultruded) through a heated die that determines the shape of the component.
- In the die, the resin is cured to form a reinforced part that can be cut to length. The hardened fiberglass pultrusion is reinforced with an internal arrangement of permanently bonded continuous glass fibers to increase its strength.
Polyurethane (PU):
- Operating Temperature: -40° to 140°F
- Chemical Compatibility Table
Installation:
- Fabrication requires just three simple operations: cutting, drilling, and sealing as described below.
- Cutting – Hand-held saws, such as hack saws (24 to 32 teeth per inch) are suitable when a few cuts are required. For frequent cutting, a circular power saw with a carbide-tipped masonry blade yields the best results. When using a power saw, dust filter masks, gloves, and long sleeve clothing should be worn.
- Drilling – Any standard twist bit, even when used with battery-powered drills will work well. Carbide-tipped drill bits are recommended.
- Sealing – To protect against future migration of corrosive elements into the cut sections, all cuts and holes should be properly sealed with a clear urethane sealer.
Operating Environment:
- Temperature Ranges – Fiberglass parts are supplied in five different materials covering distinct temperature ranges. The temperature ranges indicated are meant to be used only as a general guideline. Continual exposure to elevated temperatures reduces the strength properties of plastics and glass-reinforced fiberglass. Actual resin test data confirms that a 50% reduction in strength occurs at extremely high-temperature levels.
- Chemical Resistance – See the chemical compatibility chart for corrosion resistance. The results are based upon immersion for a 24 hour period. This is typically the “worst case” exposure to corrosion. Less severe contact such as spills, splashes, and vapor condensate will exceed the performance results listed in the table.
- Loading – Channel loading is defined with a description of each type of channel. Additional loading and design limitations for fittings and accessories are described in the appropriate section for that part.